NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS
|
Tables
No. 1 & 6 |
Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)
|
|
|
Entering
Air Temperatures |
|
Unit No.
|
Face Area
Sq.Ft
|
Air Volume
CFM
|
Coil Face Velocity
FPM
|
80°
DB 67° WB |
82°
DB 69°WB |
85°
DB 70° WB |
60 F Entering Air
Heating Capacity Standard Steam Coils |
|
Motor
Horse Power |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
1 Row BTU Per Hour
|
2 Row BTU
Per
Hour
|
Fan Diameter
|
Outlet Velocity FPM
|
1" TSP
|
1-1/4" TSP
|
1-1/2" TSP
|
226AC |
36 |
21600 |
600 |
53.28 |
62.64 |
70.92 |
84.24 |
58.32 |
68.40 |
77.40 |
92.16 |
60.68 |
71.10 |
80.85 |
96.50 |
986000 |
1729000 |
26" |
2093 |
7-1/2 |
7-1/2 |
10 |
|
|
18000 |
500 |
48.96 |
57.60 |
64.44 |
74.88 |
53.64 |
62.64 |
70.56 |
82.44 |
55.70 |
65.40 |
73.28 |
86.10 |
892000 |
153900 |
|
1744 |
5 |
7-1/2 |
7-1/2 |
|
|
14400 |
400 |
44.28 |
50.76 |
56.52 |
64.88 |
47.88 |
55.44 |
61.56 |
70.92 |
50.13 |
58.84 |
64.30 |
74.40 |
788000 |
133100 |
|
1395 |
5 |
5 |
7-1/2 |
CAPACITY CORRECTION FACTORS
Table No. 3
|
D.E.
COOLING - APPLY TO COOLING CAPACITIES IN TABLE NO. 1 |
|
Entering Air Temperatures
and Capacity Factors |
Refrigerant
Temperature |
80° DB 67° WB |
82° DB 69°WB |
85° DB 70° WB |
35° F |
1.15 |
1.14 |
1.13 |
40° F |
1.00 |
1.00 |
1.00 |
45° F |
.81 |
.83 |
.82 |
50° F |
.59 |
.62 |
.62 |
For other entering air conditions, and for water coil capacities,
see Blast Coil Bulletin No. 47A.
Table No. 4 |
STEAM HEATING -
APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Steam Pressure |
Entering Air |
2 Lbs. |
5 Lbs. |
10 Lbs. |
15 Lbs. |
0° F |
1.29 |
1.35 |
1.45 |
1.52 |
20° F |
1.18 |
1.24 |
1.32 |
1.40 |
40° F |
1.06 |
1.12 |
1.20 |
1.27 |
60° F |
.94 |
1.00 |
1.08 |
1.15 |
70° F |
.88 |
.94 |
1.02 |
1.09 |
For Steam Distributing Tube coils, multiply above correction factor
by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.
Table No. 5 |
WATER HEATING -
APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Average Water Temperatures |
Entering Air |
160 |
170 |
180 |
190 |
40° F |
.717 |
.780 |
.835 |
.891 |
50° F |
.655 |
.717 |
.780 |
.835 |
60° F |
.596 |
.655 |
.717 |
.780 |
70° F |
.528 |
.596 |
.655 |
.717 |
Factors based on 2.35 GMP per water circuit.
Specify GPM when ordering.
Table 1 indicates usual basic Unit Cooling
capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat
Percentage by use
factors in Tables 2 and 3.
Heating capacities vary with Entering Air Temperature,
Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related
values within reasonable
range.
|