NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS

Tables No. 1 & 6

Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)

 
  Entering Air Temperatures  

Unit No.

Face Area

Sq.Ft

Air Volume

CFM

Coil Face Velocity

FPM

80° DB 67° WB 82° DB 69°WB 85° DB 70° WB 60 F Entering Air Heating Capacity Standard Steam Coils   Motor Horse Power
4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows

1 Row BTU Per Hour

2 Row BTU
Per
Hour

Fan Diameter

Outlet Velocity FPM

1" TSP

1-1/4" TSP

1-1/2" TSP

226AC 36 21600 600 53.28 62.64 70.92 84.24 58.32 68.40 77.40 92.16 60.68 71.10 80.85 96.50 986000 1729000 26" 2093 7-1/2 7-1/2 10
    18000 500 48.96 57.60 64.44 74.88 53.64 62.64 70.56 82.44 55.70 65.40 73.28 86.10 892000 153900   1744 5 7-1/2 7-1/2
    14400 400 44.28 50.76 56.52 64.88 47.88 55.44 61.56 70.92 50.13 58.84 64.30 74.40 788000 133100   1395 5 5 7-1/2

CAPACITY CORRECTION FACTORS

Table No. 3
D.E. COOLING - APPLY TO COOLING CAPACITIES IN TABLE NO. 1
  Entering Air Temperatures and Capacity Factors
Refrigerant Temperature  80° DB 67° WB 82° DB 69°WB 85° DB 70° WB
35° F 1.15 1.14 1.13
40° F 1.00 1.00 1.00
45° F .81 .83 .82
50° F .59 .62 .62

For other entering air conditions, and for water coil capacities, see Blast Coil Bulletin No. 47A.

Table No. 4 STEAM HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Steam Pressure
Entering Air 2 Lbs. 5 Lbs. 10 Lbs. 15 Lbs.
0° F 1.29 1.35 1.45 1.52
20° F 1.18 1.24 1.32 1.40
40° F 1.06 1.12 1.20 1.27
60° F .94 1.00 1.08 1.15
70° F .88 .94 1.02 1.09

For Steam Distributing Tube coils, multiply above correction factor by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.

Table No. 5 WATER HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Average Water Temperatures
Entering Air 160 170 180 190
40° F .717 .780 .835 .891
50° F .655 .717 .780 .835
60° F .596 .655 .717 .780
70° F .528 .596 .655 .717

Factors based on 2.35 GMP per water circuit. Specify GPM when ordering.

Table 1 indicates usual basic Unit Cooling capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat Percentage by use
factors in Tables 2 and 3.

Heating capacities vary with Entering Air Temperature, Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related values within reasonable
range.