NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS
|
Tables
No. 1 & 6 |
Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)
|
|
|
Entering Air Temperatures |
|
Unit No.
|
Face Area
Sq.Ft
|
Air Volume
CFM
|
Coil Face Velocity
FPM
|
80°
DB 67° WB |
82°
DB 69°WB |
85°
DB 70° WB |
60 F Entering Air
Heating Capacity Standard Steam Coils |
|
Motor
Horse Power |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
4 Rows |
5 Rows |
6 Rows |
8 Rows |
1 Row BTU Per Hour
|
2 Row BTU
Per
Hour
|
Fan Diameter
|
Outlet Velocity FPM
|
1" TSP
|
1-1/4" TSP
|
1-1/2" TSP
|
220AC |
18.75 |
11250 |
600 |
27.80 |
32.70 |
37.00 |
44.00 |
30.40 |
35.70 |
40.40 |
48.10 |
31.70 |
37.15 |
42.30 |
50.40 |
514000 |
902000 |
19-1/2"
|
1940 |
5 |
5 |
7-1/2 |
|
|
9375 |
500 |
25.60 |
30.10 |
33.60 |
39.10 |
27.90 |
32.70 |
36.80 |
43.00 |
29.07 |
34.15 |
38.25 |
44.90 |
465000 |
802500 |
|
1616 |
3 |
5 |
5 |
|
|
7500 |
400 |
23.10 |
26.50 |
29.50 |
33.80 |
25.00 |
29.00 |
32.10 |
37.00 |
26.05 |
31.20 |
33.60 |
38.90 |
411000 |
694500 |
|
1293 |
3 |
3 |
5 |
CAPACITY CORRECTION FACTORS
Table No. 3 |
D.E. COOLING -
APPLY TO COOLING CAPACITIES IN TABLE NO. 1 |
|
Entering Air Temperatures
and Capacity Factors |
Refrigerant
Temperature |
80° DB 67° WB |
82° DB 69°WB |
85° DB 70° WB |
35° F |
1.15 |
1.14 |
1.13 |
40° F |
1.00 |
1.00 |
1.00 |
45° F |
.81 |
.83 |
.82 |
50° F |
.59 |
.62 |
.62 |
For other entering air conditions, and for water coil capacities,
see Blast Coil Bulletin No. 47A.
Table No. 4 |
STEAM HEATING
- APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Steam Pressure
|
Entering Air |
2 Lbs. |
5 Lbs. |
10 Lbs. |
15 Lbs. |
0° F |
1.29 |
1.35 |
1.45 |
1.52 |
20° F |
1.18 |
1.24 |
1.32 |
1.40 |
40° F |
1.06 |
1.12 |
1.20 |
1.27 |
60° F |
.94 |
1.00 |
1.08 |
1.15 |
70° F |
.88 |
.94 |
1.02 |
1.09 |
For Steam Distributing Tube coils, multiply above correction factor
by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.
Table No. 5 |
WATER HEATING
- APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Average Water
Temperatures |
Entering Air |
160 |
170 |
180 |
190 |
40° F |
.717 |
.780 |
.835 |
.891 |
50° F |
.655 |
.717 |
.780 |
.835 |
60° F |
.596 |
.655 |
.717 |
.780 |
70° F |
.528 |
.596 |
.655 |
.717 |
Factors based on 2.35 GMP per water circuit.
Specify GPM when ordering.
Table 1 indicates usual basic Unit Cooling
capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat
Percentage by use
factors in Tables 2 and 3.
Heating capacities vary with Entering Air Temperature,
Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related
values within reasonable
range.
|