NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS

Tables No. 1 & 6

Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)

 
  Entering Air Temperatures  

Unit No.

Face Area

Sq.Ft

Air Volume

CFM

Coil Face Velocity

FPM

80° DB 67° WB 82° DB 69°WB 85° DB 70° WB 60 F Entering Air Heating Capacity Standard Steam Coils   Motor Horse Power
4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows

1 Row BTU Per Hour

2 Row BTU
Per
Hour

Fan Diameter

Outlet Velocity FPM

1" TSP

1-1/4" TSP

1-1/2" TSP

213AC 8.6 5160 600 12.70 14.90 16.90 20.10 13.90 16.30 18.50 22.00 14.53 17.05 19.38 23.00 235500 413000 13" 2006 2 2 3
    4300 500 11.70 13.70 15.40 17.80 12.80 14.90 16.80 19.63 13.32 15.68 17.66 20.50 213200 367600   1672 1-1/2 2 2
    3440 400 10.60 12.10 13.50 15.40 11.40 13.20 14.70 16.90 11.97 13.85 15.40 17.86 188300 318000   1337 1 1-1/2 1-1/2

 

CAPACITY CORRECTION FACTORS

Table No. 3 D.E. COOLING - APPLY TO COOLING CAPACITIES IN TABLE NO. 1
  Entering Air Temperatures and Capacity Factors
Refrigerant Temperature  80° DB 67° WB 82° DB 69°WB 85° DB 70° WB
35° F 1.15 1.14 1.13
40° F 1.00 1.00 1.00
45° F .81 .83 .82
50° F .59 .62 .62

For other entering air conditions, and for water coil capacities, see Blast Coil Bulletin No. 47A.

 

Table No. 4 STEAM HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Steam Pressure
Entering Air 2 Lbs. 5 Lbs. 10 Lbs. 15 Lbs.
0° F 1.29 1.35 1.45 1.52
20° F 1.18 1.24 1.32 1.40
40° F 1.06 1.12 1.20 1.27
60° F .94 1.00 1.08 1.15
70° F .88 .94 1.02 1.09

For Steam Distributing Tube coils, multiply above correction factor by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.

 

Table No. 5 WATER HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Average Water Temperatures
Entering Air 160 170 180 190
40° F .717 .780 .835 .891
50° F .655 .717 .780 .835
60° F .596 .655 .717 .780
70° F .528 .596 .655 .717

Factors based on 2.35 GMP per water circuit. Specify GPM when ordering.

Table 1 indicates usual basic Unit Cooling capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat Percentage by use
factors in Tables 2 and 3.

Heating capacities vary with Entering Air Temperature, Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related values within reasonable
range.