    | NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS |   
    | Tables 
      No. 1 & 6 | Cooling Capacity DE Coils - (Tons at 40° F Refrigerant) |  |   
    |  | Entering Air Temperatures |  |   
    | Unit No. | Face Area
 Sq.Ft
 | Air Volume
 CFM
 | Coil Face Velocity
 FPM
 | 80° 
      DB 67° WB | 82° 
      DB 69°WB | 85° 
      DB 70° WB | 60 F Entering Air 
      Heating Capacity Standard Steam Coils |  | Motor 
      Horse Power |   
    | 4 Rows | 5 Rows | 6 Rows | 8 Rows | 4 Rows | 5 Rows | 6 Rows | 8 Rows | 4 Rows | 5 Rows | 6 Rows | 8 Rows | 1 Row BTU Per Hour | 2 Row BTU Per
 Hour
 | Fan Diameter | Outlet Velocity FPM | 1" TSP | 1-1/4" TSP | 1-1/2" TSP |   
    | 211AC | 7.12 | 4272 | 600 | 10.50 | 12.30 | 14.00 | 16.60 | 11.50 | 13.50 | 15.20 | 18.20 | 12.02 | 14.10 | 16.00 | 19.00 | 195000 | 342000 | 11-3/8" | 1892 | 1-1/2 | 2 | 2 |   
    |  |  | 3560 | 500 | 9.65 | 11.30 | 12.70 | 14.75 | 10.55 | 12.30 | 13.90 | 16.20 | 11.02 | 12.95 | 14.51 | 16.92 | 169800 | 304500 |  | 1577 | 1-1/2 | 1-1/2 | 1-1/2 |   
    |  |  | 2848 | 400 | 8.71 | 10.00 | 11.10 | 12.75 | 9.43 | 10.90 | 12.00 | 13.95 | 9.90 | 11.45 | 12.72 | 14.75 | 156000 | 263500 |  | 1261 | 1 | 1 | 1-1/2 |    CAPACITY CORRECTION FACTORS 
   
    | Table No. 3 | D.E. COOLING - 
      APPLY TO COOLING CAPACITIES IN TABLE NO. 1 |   
    |  | Entering Air Temperatures 
      and Capacity Factors |   
    | Refrigerant 
      Temperature | 80° DB 67° WB | 82° DB 69°WB | 85° DB 70° WB |   
    | 35° F | 1.15 | 1.14 | 1.13 |   
    | 40° F | 1.00 | 1.00 | 1.00 |   
    | 45° F | .81 | .83 | .82 |   
    | 50° F | .59 | .62 | .62 |  For other entering air conditions, and for 
  water coil capacities, see Blast Coil Bulletin No. 47A.   
   
    | Table No. 4 | STEAM HEATING - 
      APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |   
    |  | Steam Pressure |   
    | Entering Air | 2 Lbs. | 5 Lbs. | 10 Lbs. | 15 Lbs. |   
    | 0° F | 1.29 | 1.35 | 1.45 | 1.52 |   
    | 20° F | 1.18 | 1.24 | 1.32 | 1.40 |   
    | 40° F | 1.06 | 1.12 | 1.20 | 1.27 |   
    | 60° F | .94 | 1.00 | 1.08 | 1.15 |   
    | 70° F | .88 | .94 | 1.02 | 1.09 |  For Steam Distributing Tube coils, multiply 
  above correction factor by .95 for 8 fins per inchand by .80 for 6-1/2 fins per inch.
   
   
    | Table No. 5 | WATER HEATING - 
      APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |   
    |  | Average Water Temperatures |   
    | Entering Air | 160 | 170 | 180 | 190 |   
    | 40° F | .717 | .780 | .835 | .891 |   
    | 50° F | .655 | .717 | .780 | .835 |   
    | 60° F | .596 | .655 | .717 | .780 |   
    | 70° F | .528 | .596 | .655 | .717 |  Factors based on 2.35 GMP per water circuit. 
  Specify GPM when ordering. Table 1 indicates usual basic Unit Cooling 
  capacities at conventional operating conditions whichcan be modified for variations in Refrigerant Temperature and Sensible Heat 
  Percentage by use
 factors in Tables 2 and 3.
 Heating capacities vary with Entering Air Temperature, 
  Steam Pressures and Water Temperaturesand can be modified by factors in Tables 4 and 5, interpolating for related 
  values within reasonable
 range.
 |