NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS
|
Tables
No. 1 & 6 |
Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)
|
|
|
Entering Air Temperatures |
|
Unit No.
|
Face Area
Sq.Ft
|
Air Volume
CFM
|
Coil Face Velocity
FPM
|
80°
DB 67° WB |
82°
DB 69°WB |
85°
DB 70° WB |
60
F Entering Air Heating Capacity Standard Steam Coils |
|
Motor
Horse Power |
4
Rows |
5
Rows |
6
Rows |
8
Rows |
4
Rows |
5
Rows |
6
Rows |
8
Rows |
4
Rows |
5
Rows |
6
Rows |
8
Rows |
1 Row BTU Per Hour
|
2 Row BTU
Per
Hour
|
Fan Diameter
|
Outlet Velocity FPM
|
1" TSP
|
1-1/4" TSP
|
1-1/2" TSP
|
111AC |
3.62 |
2172 |
600 |
5.32 |
6.25 |
7.10 |
8.43 |
5.84 |
6.84 |
7.73 |
9.20 |
6.12 |
7.17 |
8.15 |
9.65 |
99100 |
181000 |
11-3/8"
|
1926 |
3/4 |
1 |
1 |
|
|
1810 |
500 |
4.90 |
5.75 |
6.45 |
7.49 |
5.35 |
6.25 |
7.05 |
8.25 |
5.61 |
6.60 |
7.40 |
8.60 |
88700 |
154800 |
|
1605 |
3/4 |
3/4 |
1 |
|
|
1448 |
400 |
4.43 |
5.08 |
5.65 |
6.48 |
4.79 |
5.54 |
6.15 |
7.09 |
5.04 |
5.83 |
6.48 |
7.48 |
79300 |
133900 |
|
1284 |
1/2 |
1/2 |
3/4 |
CAPACITY CORRECTION FACTORS
Table No. 3
|
D.E. COOLING -
APPLY TO COOLING CAPACITIES IN TABLE NO. 1 |
|
Entering Air Temperatures
and Capacity Factors |
Refrigerant
Temperature |
80° DB 67° WB |
82° DB 69°WB |
85° DB 70° WB |
35° F |
1.15 |
1.14 |
1.13 |
40° F |
1.00 |
1.00 |
1.00 |
45° F |
.81 |
.83 |
.82 |
50° F |
.59 |
.62 |
.62 |
For other entering air conditions, and for water coil capacities,
see Blast Coil Bulletin No. 47A.
Table No. 4 |
STEAM HEATING -
APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Steam Pressure |
Entering Air |
2 Lbs. |
5 Lbs. |
10 Lbs. |
15 Lbs. |
0° F |
1.29 |
1.35 |
1.45 |
1.52 |
20° F |
1.18 |
1.24 |
1.32 |
1.40 |
40° F |
1.06 |
1.12 |
1.20 |
1.27 |
60° F |
.94 |
1.00 |
1.08 |
1.15 |
70° F |
.88 |
.94 |
1.02 |
1.09 |
For Steam Distributing Tube coils, multiply above correction factor
by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.
Table No. 5 |
WATER HEATING -
APPLY TO HEATING CAPACITIES IN TABLE NO. 1 |
|
Average Water Temperatures |
Entering Air |
160 |
170 |
180 |
190 |
40° F |
.717 |
.780 |
.835 |
.891 |
50° F |
.655 |
.717 |
.780 |
.835 |
60° F |
.596 |
.655 |
.717 |
.780 |
70° F |
.528 |
.596 |
.655 |
.717 |
Factors based on 2.35 GMP per water circuit.
Specify GPM when ordering.
Table 1 indicates usual basic Unit Cooling
capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat
Percentage by use
factors in Tables 2 and 3.
Heating capacities vary with Entering Air Temperature,
Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related
values within reasonable
range.
|