NOMINAL CAPACITIES OF KENNARD CORPORATION AIR HANDLERS

Tables No. 1 & 6

Cooling Capacity DE Coils - (Tons at 40° F Refrigerant)

 
  Entering Air Temperatures  

Unit No.

Face Area

Sq.Ft

Air Volume

CFM

Coil Face Velocity

FPM

80° DB 67° WB 82° DB 69°WB 85° DB 70° WB 60 F Entering Air Heating Capacity Standard Steam Coils   Motor Horse Power
4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows 4 Rows 5 Rows 6 Rows 8 Rows

1 Row BTU Per Hour

2 Row BTU
Per
Hour

Fan Diameter

Outlet Velocity FPM

1" TSP

1-1/4" TSP

1-1/2" TSP

110AC 2.29 1374 600 3.40 4.00 4.53 5.38 3.72 4.37 4.95 5.89 3.87 4.54 5.16 6.16 62700 110000 9-3/4" 1832 1/2 3/4 3/4
    1145 500 3.13 3.68 4.12 4.79 3.40 4.00 4.50 5.26 3.55 4.17 4.67 5.50 56750 97900   1526 1/2 1/2 1/2
    916 400 2.82 3.24 3.60 4.14 3.06 3.54 3.93 4.53 3.18 3.69 4.10 4.79 50200 84700   1221 1/3 1/2 1/2

 

CAPACITY CORRECTION FACTORS

Table No. 3 D.E. COOLING - APPLY TO COOLING CAPACITIES IN TABLE NO. 1
  Entering Air Temperatures and Capacity Factors
Refrigerant Temperature  80° DB 67° WB 82° DB 69°WB 85° DB 70° WB
35° F 1.15 1.14 1.13
40° F 1.00 1.00 1.00
45° F .81 .83 .82
50° F .59 .62 .62

For other entering air conditions, and for water coil capacities, see Blast Coil Bulletin No. 47A.

 

Table No. 4 STEAM HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Steam Pressure
Entering Air 2 Lbs. 5 Lbs. 10 Lbs. 15 Lbs.
0° F 1.29 1.35 1.45 1.52
20° F 1.18 1.24 1.32 1.40
40° F 1.06 1.12 1.20 1.27
60° F .94 1.00 1.08 1.15
70° F .88 .94 1.02 1.09

For Steam Distributing Tube coils, multiply above correction factor by .95 for 8 fins per inch
and by .80 for 6-1/2 fins per inch.

 

Table No. 5 WATER HEATING - APPLY TO HEATING CAPACITIES IN TABLE NO. 1
  Average Water Temperatures
Entering Air 160 170 180 190
40° F .717 .780 .835 .891
50° F .655 .717 .780 .835
60° F .596 .655 .717 .780
70° F .528 .596 .655 .717

Factors based on 2.35 GMP per water circuit. Specify GPM when ordering.

Table 1 indicates usual basic Unit Cooling capacities at conventional operating conditions which
can be modified for variations in Refrigerant Temperature and Sensible Heat Percentage by use
factors in Tables 2 and 3.

Heating capacities vary with Entering Air Temperature, Steam Pressures and Water Temperatures
and can be modified by factors in Tables 4 and 5, interpolating for related values within reasonable
range.